Every fire-rated wall and floor in a plant or building is only as strong as its weakest opening. Cables, pipes and ducts have to pass through those barriers, and each hole cut for them is a path for fire, smoke and hot gases. Firestop mortar is one of the most reliable ways to close those openings and give the wall or floor back its fire rating.
This guide explains what firestop mortar is, when to choose it over other seals, how to install it around service penetrations, and how to read the fire ratings that come with it.
Quick answer: Firestop mortar is a dry, mineral-based powder mixed with water on site and trowelled or poured into openings around cables, pipes and ducts in fire-rated walls and floors. Once cured, it restores the barrier’s fire resistance, blocking fire, smoke and heat for the rated period.
What is firestop mortar?
Firestop mortar is a passive fire protection material used to seal service penetrations. Most products, including CharCoat FM, are based on gypsum with lightweight fillers such as perlite. Mixed with water, the mortar sets into a solid, heat-absorbing mass that fills the opening around each service.
It is a firestopping product, not a fireproofing coating. Fireproofing protects a structural element such as a steel beam; firestopping seals the gaps in a fire-rated barrier. Our guide to fireproofing vs firestopping explains the difference in detail.
Why service penetrations are a weak point
A fire-rated wall or floor is designed to hold a fire in one compartment for a set time. Every opening cut for services breaks that design.
Without a tested seal, a penetration lets:
- Flames and hot gases pass straight into the next compartment.
- Smoke spread along cable routes and service shafts, often faster than the fire itself.
- Heat conduct along metal pipes and cable trays and ignite materials on the other side.
In industrial plants the stakes are higher still. A fire that spreads from a cable gallery into a switch room or control room can shut down a whole facility. That is why firestop and penetration seals sit alongside cable coatings and structural fireproofing in a complete passive fire protection plan.
When to use firestop mortar (and when another seal fits better)
Mortar is not the only way to seal a penetration. The right choice depends on the opening size, the services passing through and whether you will need to add services later.
| Seal type | Best for | Strengths | Watch out for |
|---|---|---|---|
| Firestop mortar | Medium to large openings in masonry and concrete; floors with mixed services | Solid, durable, high fire ratings; can carry load in floors | Harder to re-enter for new services; needs curing time |
| Intumescent sealant | Small gaps around single cables and pipes; finishing joints | Flexible, quick to apply | Limited to small annular gaps |
| Coated firestop panel | Large openings in flexible and rigid walls where services change often | Lightweight; easy to cut and re-penetrate | Lower mechanical strength than mortar |
| Collars and wraps | Plastic pipes | Close the gap as the pipe softens in a fire | Used with the main seal, not on their own |
Choose firestop mortar when:
- The opening is in concrete, brick or blockwork and needs a robust, permanent seal.
- The seal is in a floor and may be walked on or need to carry load.
- Many mixed services (cables, trays, pipes) pass through one opening.
- You need a high fire rating, such as up to 4 hours with CharCoat FM.
For openings where services change often, a coated panel such as CharCoat FP with CharCoat IS intumescent sealant may be the better fit.
How firestop mortar works
Firestop mortar protects a penetration in three ways:
- It fills the opening completely. Packed around and between services, it leaves no open path for flames or smoke.
- It expands slightly as it cures. CharCoat FM cures by hydraulic action and expands about 1%, locking tightly against the services and the opening edges.
- It absorbs and slows heat. Gypsum holds chemically bound water that is released as steam when heated, which slows the temperature rise on the protected side.
The result is a seal that keeps fire, smoke and heat in the compartment of origin for the rated time.

How to install firestop mortar around service penetrations
Always follow the manufacturer’s technical data sheet and the tested system for your exact wall or floor. The general sequence is:
- Confirm the tested detail. Check that the wall or floor type, its thickness, the services and the opening size all match a tested and classified system.
- Prepare the opening. Remove dust, debris and loose material. Make sure services are supported at the spacings the tested detail requires.
- Fit formwork for floors. Fix temporary shuttering below floor openings so pourable mortar stays in place while it sets.
- Mix the mortar. Add the powder to clean water at the ratio on the data sheet. Mix stiffer for walls and more fluid for pouring into floors.
- Apply to full depth. Trowel the mortar into wall openings or pour it into floor openings to the depth the tested system specifies. Work it between cables and around pipes so no voids remain.
- Finish and seal. Smooth the surface flush with the wall or floor. Seal small gaps around individual cables with intumescent sealant where the tested detail calls for it.
- Let it cure. CharCoat FM sets within 1 hour; its rated fire performance applies after a 1-month curing period.
- Label and record. Give each seal a unique reference, label it, and photograph it before, during and after installation.
Understanding fire ratings for penetration seals
Fire ratings tell you how long a seal holds back fire and heat. Two systems are common.
European ratings: EI under EN 1366-3 and EN 13501-2
In Europe and many export markets, penetration seals are tested to EN 1366-3 and classified to EN 13501-2. A classification such as EI 120 combines two criteria:
- E (integrity): how long the seal stops flames and hot gases passing through.
- I (insulation): how long it keeps the unexposed side from heating up beyond the test limit.
The number is the time in minutes. EI 120 means 2 hours, and EI 240 means 4 hours.
North American ratings: F and T under ASTM E814 / UL 1479
In North America, through-penetration firestops are tested to ASTM E814 or UL 1479. The F rating measures how long the system stops fire passing through. The T rating measures how long it limits heat transfer to the unexposed side.
Whichever system applies, never choose a tested detail with a lower rating than the wall or floor you are sealing. Our article on fire resistance ratings explains how ratings are set for whole facilities.
Common mistakes that make penetration seals fail
Most failed seals come down to installation, not the product. Avoid these:
- Using an untested combination. Mixing products from different manufacturers in one opening, without test evidence, voids the rating.
- Leaving voids. Mortar that does not reach between bundled cables or to full depth leaves a hidden path for fire.
- Ignoring plastic pipes. Plastic pipes soften and collapse in a fire, so tested details usually add a collar, wrap or intumescent sealant.
- Poor service support. Cables and pipes that are not supported within the certified spacing can pull the seal apart in a fire.
- Confusing reaction to fire with fire resistance. A Class B or Class 0 material rating is not a fire-resistance rating.
- Breaking the seal later. New services pushed through an existing seal, without re-sealing, are one of the most common faults found in inspections.
Inspection and documentation checklist
The FIS best-practice guide on firestopping service penetrations, produced with the ASFP, BESA and others, recommends a clear record for every seal. As a minimum:
- ☐ The tested system and its classification certificate are on file.
- ☐ Each seal has a unique reference number and a label.
- ☐ Photos were taken before, during and after installation.
- ☐ Someone other than the installing operative inspected the seal.
- ☐ Product purchase records and installer competence records are kept.
- ☐ Records are handed over to the building or plant owner.
Good records make future inspections faster and show auditors and insurers that every opening is accounted for.
CharCoat FM: firestop mortar for walls and floors
CharCoat FM is a gypsum and perlite firestop mortar for sealing service penetrations in fire-rated walls and floors.
| Property | CharCoat FM |
|---|---|
| Fire resistance | Up to 4 hours in concrete, brick and gypsum substrates (after 1-month cure) |
| Classification | EN 13501-2 |
| Services sealed | Cables, bundled cables, cable trays and racks, steel, copper, Alupex and plastic pipes, ventilation ducts |
| Substrates | Concrete, brick, Leca, gypsum, corrosion-protected steel |
| Application | Trowel or pour after mixing with water |
| Setting time | Fully set within 1 hour |
| Finish | Off-white; can be sanded, drilled and painted |
| Other | Load-bearing without reinforcement; low VOC; BREEAM M1 tested |
It is used in power facilities, industrial plants and commercial and residential buildings. Where cables run on through the compartment, pair it with CharCoat CC cable coating to stop fire spreading along the cable route itself.
Plan firestopping early
Penetration seals are cheapest and most reliable when they are planned with the services, not added at handover. Our guide on when to include fire protection in a new project covers how to build it into the design stage.

Need help choosing the right seal for your walls and floors? Talk to a CharCoat engineer about your project.
FAQ
What is firestop mortar used for?
Firestop mortar seals openings where cables, pipes, cable trays and ducts pass through fire-rated walls and floors. Once cured, it restores the barrier’s fire resistance and stops fire, smoke and heat spreading into the next compartment.
How long does firestop mortar last?
A correctly installed mortar seal is a permanent part of the wall or floor and needs no routine replacement. It should be inspected periodically and re-sealed whenever new services are added or the seal is damaged.
Can firestop mortar be used in floors?
Yes. Mortar is well suited to floor penetrations because it can be poured to a level finish and some products, including CharCoat FM, can carry load without reinforcement. Temporary formwork holds the mortar in place while it sets.
What fire rating does firestop mortar provide?
Ratings depend on the product, the wall or floor and the services sealed. CharCoat FM provides up to 4 hours of fire resistance in concrete, brick and gypsum substrates, classified to EN 13501-2, after a 1-month curing period.
Is firestop mortar better than firestop sealant?
Neither is better in every case. Mortar suits medium to large openings and floors with many services. Intumescent sealant suits small gaps around single cables and pipes. Many tested systems use both together.
Can you add new cables through an existing mortar seal?
Yes, but the seal must be restored afterwards. Drill or core through the cured mortar, install the new service, then re-seal the opening with the same tested system so the fire rating is maintained.